> For the complete documentation index, see [llms.txt](https://docs.efento.io/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://docs.efento.io/nb-iot-loggers/installation/logger-specific-installation-guidelines/water-rope.md).

# Water rope

The Efento Water Rope Logger is designed for early flood and water leak detection across large areas or along critical piping and infrastructure. Unlike point-leak sensors that detect water only at one localized spot, the water sensing cable detects conductive liquids across its entire length.

## **How the Water Sensing Cable Works**

The water sensing cable (water rope) consists of two conductive polymer-coated wires embedded alongside non-conductive carrier threads inside a durable outer braid:

1. **Passive Open Circuit (Dry State):** When dry, the conductive polymer wires remain electrically isolated from one another. The circuit behaves as an open contact with near-infinite resistance.
2. **Conductivity Bridge (Leak State):** When water or another conductive liquid touches any part of the cable, the liquid penetrates the braid and creates a conductive bridge between the sensing wires. This causes an immediate drop in resistance.
3. **Triggering the Alert:** The logger senses this resistance drop and instantly triggers a water leak alarm.
4. **Reusability:** The sensing cable is fully reusable. Once the source of the leak is resolved and the cable is dried, its electrical resistance returns to normal, and the logger automatically clears the alarm state.

## **Package Contents & Required Tools**

Before starting the installation, ensure you have the following items:

* Efento Water Rope Logger.
* Sensing cable (water rope) of the desired length.
* Non-sensing leader cable (if the logger is mounted away from the sensing zone).
* End termination cap / plug (terminator).
* Surface mounting clips or cable guide brackets.
* Degreasing cleaner (e.g., Isopropyl alcohol / IPA) and a clean cloth.

## **Step-by-Step Installation**

{% stepper %}
{% step %}

### **Plan the Cable Route**

* Identify potential leak sources, such as air conditioning units (HVAC/CRAC), piping runs, pumps, valves, or perimeter walls in server rooms, archives, or basements.
* Route non-sensing leader cable between the wall-mounted logger and the detection zone, and begin the sensing cable only where liquid detection is required.
  {% endstep %}

{% step %}

### **Prepare the Surface**

* Thoroughly vacuum and degrease the floor surface along the planned path.
* **Important:** Remove metal debris, drywall dust, and conductive dirt, as damp construction dust can cause false alarms.
  {% endstep %}

{% step %}

### **Install Mounting Clips**

* Place adhesive or screw-mounted cable clips every **0.5 m to 1.0 m** along straight runs, and closer together at bends or near corners.
* Press clips firmly onto the cleaned, degreased surface.
  {% endstep %}

{% step %}

### **Lay and Secure the Cable**

* Snap the cable into the clips so it rests flat against the floor. The cable must touch the floor surface to detect thin films of water before flooding deepens.
* Keep the cable straight and lightly tensioned, but do not stretch it tightly.
* Maintain a minimum bending radius of **50 mm** around corners. Do not kink, pinch, or bend the cable at a sharp 90° angle.
  {% endstep %}

{% step %}

### **Verify the cable assembly**

* Before installation, check that the leader cable, sensing cable, and end termination cap are securely connected.
* The cable assembly is supplied preassembled, so no additional wiring or connector installation is required.
* Mount the logger body on the wall or DIN rail at a safe height (well above potential standing water).

<figure><img src="https://740246929-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FGPFUI36OraG706yJS7dJ%2Fuploads%2FuabzAoeA0xQLyq3UhHDG%2Fwater_rope_installation.png?alt=media&amp;token=1aa00b25-8b4c-48dc-83f1-394d3f3c8d02" alt="" width="375"><figcaption></figcaption></figure>
{% endstep %}

{% step %}

### **Commissioning & Functional Verification**

* Power up the logger and confirm that the mobile app or cloud dashboard indicates **OK** status (no leak).
* Moisten a clean cloth with tap water and wrap it around any section of the sensing cable for a few seconds.
* Confirm that the logger immediately registers a **Leak Detected** alarm.
* Remove the wet cloth and thoroughly wipe the cable dry with a clean paper towel.
* Verify that the logger clears the alarm and returns to the **OK** state.
  {% endstep %}
  {% endstepper %}

## **Installation best practices**

| Recommended                                                                                                              | Avoid                                                                                                                                                |
| ------------------------------------------------------------------------------------------------------------------------ | ---------------------------------------------------------------------------------------------------------------------------------------------------- |
| **Ensure floor contact:** Keep the cable touching the floor so it catches pooling water early.                           | **Do not tape over the cable:** Never use adhesive tape over the sensing braid, as adhesive blocks water from contacting the sensing cores.          |
| **Clean surfaces first:** Clean the floor prior to laying the cable to avoid dust-induced false alarms.                  | **Do not pinch or crimp:** Never drive over the cable with carts, crush it under furniture legs, or bend it sharply.                                 |
| **Use leader cables:** Use regular non-sensing extension wire to travel from the wall-mounted logger to the floor.       | **Keep the logger unit dry:** Install the main logger enclosure away from areas where water may pool or where it could be directly exposed to leaks. |
| **Cap the cable end:** Always install the protective termination cap to prevent contaminants from bridging the end pins. | **Avoid aggressive chemicals:** Do not expose the cable to harsh organic solvents or corrosive acids that degrade polymer conductors.                |


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://docs.efento.io/nb-iot-loggers/installation/logger-specific-installation-guidelines/water-rope.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.