4-20 mA
Efento 4–20 mA loggers are engineered to measure the standard analog output of industrial sensor probes and seamlessly transmit this data over NB-IoT networks directly to Efento Cloud or your custom backend server.
Channel compatibility and specifications
Each logger can support up to three independent analog channels, making it fully compatible with:
2-wire probes
3-wire PNP / NPN probes
4-wire probes
The logger is capable of measuring currents across a broad range of -24 to 24 mA, with a high measurement resolution of 0.001 mA. The internal shunt resistance (Rs) for each channel is 3 Ω.
Connecting the probes
To wire your 4–20 mA sensors to the terminal blocks, you must first access the Printed Circuit Board (PCB) by opening the logger's enclosure.
Open the enclosure
Refer to the Inserting the SIM card and powering on section for full details on opening your specific casing model:
IP30 Enclosures: Use a flat tool or small screwdriver to gently pry open the back panel. remove the front cover, unscrew the internal protective plastic shield (2 screws), and lift out the mainboard.
IP65 Enclosures: Unscrew and remove the external screws securing the front and back panels together, remove the front cover, unscrew the internal protective plastic shield (2 screws), and lift out the mainboard.
IP67 Enclosures: Remove the four screws securing the lid and carefully lift it off. The expansion board is directly accessible after opening the enclosure, so no additional disassembly is required to connect or disconnect the probe.
Wire to the terminal blocks
Connect the individual wire leads of your probe to the appropriate screw terminal channels on the PCB (Sensor probe wiring and configurations). Double-check your sensor's data sheet for correct pinouts to prevent polarity reversal.
Secure the hardware settings
Before closing the device, verify that your Sensor Power DIP switch (Power configuration) and your Channel DIP switches are correctly positioned to match your specific probe type (Sensor probe wiring and configurations).
Reassemble the device
Connect the power board connector and firmly seat the mainboard back into its designated position. For IP30 and IP65 versions, place the internal plastic cover over the board and secure it with the two internal screws. Then close the outer casing by snapping the back panel shut (IP30), evenly tightening the external cover screws (IP65), or refitting the lid and tightening the four screws evenly while ensuring the gasket is correctly seated (IP67).
Power configuration
The logger offers two distinct operational modes for supplying electrical power to your connected sensors: logger-powered (passive mode) and externally powered (active mode).
Sensor probe wiring and configurations
By default, Efento 4–20 mA loggers are equipped with 2 measurement channels. A 3rd channel is optional and must be specified at the time of ordering.
Each channel must be manually configured to match your specific probe type (2-wire, 3-wire, or 4-wire) using the dedicated hardware switches located directly on the PCB:
Channel 1 configuration: adjusted using DIP switches J1 and J2.
Channel 2 configuration: adjusted using DIP switches J3 and J4.
Channel 3 configuration (optional): adjusted using DIP switches J5 and J6.
Wiring schemes depend on the selected power source type. For the wiring diagram of the used probe and external power supply contact the corresponding manufacturers.
Logger-powered probes (passive mode)
Externally powered probes (active mode)