0-10 V
Efento 0–10 V loggers are engineered to measure analog voltage signals and seamlessly transmit this data over NB-IoT networks directly to Efento Cloud or your custom backend server. They can be used to monitor any standard sensor probe equipped with a 0–10 V interface or simply to measure baseline voltage across a variety of industrial applications.
Channel compatibility and specifications
Each logger can support up to three independent analog channels.
The logger features a wide input voltage measurement range of 0 to 24 V, boasting a high resolution (LSB) of 1.6 mV and an input impedance of 1M Ω.
Connecting the probes
To wire your 0–10 V sensors to the terminal blocks, you must first access the Printed Circuit Board (PCB) by opening the logger's enclosure.
Open the enclosure
Refer to the Inserting the SIM card and powering on section for full details on opening your specific casing model:
IP30 Enclosures: Use a flat tool or small screwdriver to gently pry open the back panel. remove the front cover, unscrew the internal protective plastic shield (2 screws), and lift out the mainboard.
IP65 Enclosures: Unscrew and remove the external screws securing the front and back panels together, remove the front cover, unscrew the internal protective plastic shield (2 screws), and lift out the mainboard.
IP67 Enclosures: Remove the four screws securing the lid and carefully lift it off. The expansion board is directly accessible after opening the enclosure, so no additional disassembly is required to connect or disconnect the probe.
Wire to the terminal blocks
Connect the individual wire leads of your probe to the appropriate screw terminal channels on the PCB (Power configuration / wiring). Double-check your sensor's data sheet for correct pinouts to prevent polarity reversal.
Secure the hardware settings
Before closing the device, verify that your Sensor Power DIP switch (Power configuration / wiring) is correctly positioned to match your specific probe type.
Reassemble the device
Connect the power board connector and firmly seat the mainboard back into its designated position. For IP30 and IP65 versions, place the internal plastic cover over the board and secure it with the two internal screws. Then close the outer casing by snapping the back panel shut (IP30), evenly tightening the external cover screws (IP65), or refitting the lid and tightening the four screws evenly while ensuring the gasket is correctly seated (IP67).
Power configuration / wiring
The logger offers two distinct operational modes for supplying electrical power to your connected sensors: logger-powered (passive mode) and externally powered (active mode).