4-20 mA / 0-10 V

Efento 4–20 mA and 0–10 V loggers include configuration options that allow the measurement channel to be adapted to the characteristics of the connected probe or transmitter.

The available settings include manual calibration of the measurement input and adjustment of the startup time required by the connected sensor before a measurement is taken.

Manual calibration

Efento 4–20 mA and 0-10 V loggers are factory-calibrated and provide accurate current measurements by default. However, if necessary, users may perform a manual calibration to further improve measurement precision. Calibration is carried out at four reference points (4 mA, 12 mA, 16 mA, and 20 mA for a 4–20 mA loggers and 1 V, 2 V, 6 V, 10 V for 0-10 V loggers) with a loop calibrator to supply the logger with a known, stable current / voltage.

Configuration using the Efento mobile application

To set the starting value, connect to the device and tap the gear icon. Go to Channel settings, select Calibration for the relevant channel, enter the required starting value, and save the changes.

Configurable parameters

Parameter
Description
Configuration Options

Startup time

Defines how long the logger waits after powering the connected sensor before taking a measurement, allowing the sensor to stabilize. The required value should be based on the sensor manufacturer’s specifications.

Range: 0 to 300,000 ms

Configuration using the Efento mobile application

All parameters described above can be configured using the Efento mobile application in the Nearby Devices section.

Connect to the logger, tap the gear icon, open Channel settings, and select Settings for the required channel.