> For the complete documentation index, see [llms.txt](https://docs.efento.io/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://docs.efento.io/nb-iot-loggers/configuration/device-settings/transmission-interval.md).

# Transmission interval

The **Transmission Interval** defines how frequently the logger connects to the cellular network to send stored measurement data to the server. Under standard operation, data is uploaded at this regular interval (1 minute - 7 days), with each transmission capable of containing multiple accumulated measurements to optimize bandwidth.

If a configured [**alarm rule**](https://docs.efento.io/nb-iot-loggers/configuration/device-settings/rules.md) or threshold is triggered, the logger immediately initiates an additional, out-of-schedule transmission to report the event.

Each transmission frame also informs the server of the scheduled timestamp for the next planned communication, allowing the platform to detect missing or delayed check-ins. Depending on your configuration, transmissions can either require an acknowledgment (ACK) from the server to confirm receipt or operate without confirmation.

Because radio communication consumes significant power, the length of the transmission interval has a direct impact on the [**device's battery lifespan**](https://docs.efento.io/nb-iot-loggers/operation/battery-life.md) - longer intervals significantly extend battery runtime.

## **Transmission acknowledgment (ACK)**

Additionally, it is possible to configure how often the message sent by the logger requires confirmation of receipt by the server (ACK). If the ACK is not received by the logger, it will retransmit the data to the server. The confirmation frame (ACK) is used also to send a new configuration to the device.

{% hint style="warning" %}
In order to make sure that all the measurements reach the server, set the ACK interval to “Always”. In case of any transmission issues, the logger will try to resend the data until it succeeds.
{% endhint %}

Type of messages sent by the loggers depend on the use case. If your use case requires all the messages to reach the server, then you should set the logger to always require the ACK. If your use case is not critical, and you are aware that some data frames can be lost, you can set the device to require the confirmation less often (e.g. every 24 hours).

{% hint style="info" %}
Devices receive new configurations from the server through ACK frames. Keep this in mind when setting the ACK interval to more than 24 hours.
{% endhint %}

Logger stores up to **100 000 measurements** in its memory (pulse counters - 50,000 measurements). In case of any issues that block the communication between logger and server (network issue, server issue, etc.), if the ACKs are enabled, the logger will resent the missing data to the server.

### **Transmission Retry Algorithm & Back-Off Timer**

When **ACKs (acknowledgments) are enabled**, the logger verifies whether each transmitted CoAP data packet has been successfully received and confirmed by the server. If the server does not confirm receipt, or if a transmission fails due to temporary network issues, the logger activates an automatic **back-off retry algorithm** to conserve battery while guaranteeing data delivery.

**How the Retry Mechanism Works:**

1. **Local Buffering:**\
   Unacknowledged measurements are not discarded. They remain safely stored in the logger’s non-volatile memory (up to 100,000 measurements).
2. **Exponential Back-Off Schedule:**\
   To prevent rapid battery depletion and avoid flooding the cellular network during an outage, the device does not immediately re-attempt transmission. Instead, it schedules retries according to progressive time intervals:
   * **Initial Retries:** The logger executes short-interval retries (typically within a few minutes) to recover from brief signal drops.
   * **Progressive Back-Off:** If transmission failures persist, the retry intervals increase progressively (e.g., doubling the wait time).
   * **Disabled Mode (Deep Sleep):** If the device repeatedly fails to attach to the cellular network or reach the server, the cellular modem is completely powered off (power-gated) and the logger enters *Disabled Mode* for a defined base period (e.g., 90 minutes). During this time, the logger continues taking measurements on schedule and storing them in memory.
3. **Restoring Connectivity & Backfill:**
   * When the back-off timer expires, the modem wakes up, reconnects to the network, and attempts to deliver the unsent data.
   * If a human operator presses the physical power button on the device or uses the "Trigger transmission" option in the Efento mobile application in Nearby devices, the back-off timer is immediately overridden and the modem wakes up for an immediate transmission attempt.
4. **Data Backlog Delivery:**\
   Once a transmission succeeds and an ACK is received, the logger automatically transmits the accumulated backlog of historical measurements in chronological order until all stored data is fully synchronized with the server.

## **Configurable parameters**

| Parameter                 | Descritpion                                                                           | Range                   |
| ------------------------- | ------------------------------------------------------------------------------------- | ----------------------- |
| **Transmission interval** | Defines how often the measurements are sent to the server.                            | 60 - 604 800 seconds    |
| **ACK interval**          | A confirmation sent by the server that a transmission has been successfully received. | 180 - 2 592 000 seconds |

## **Configuration methods**

You can configure these settings in several ways:

* **Remotely from server** – see the [**Integrations** ](https://docs.efento.io/nb-iot-loggers/integrations/direct-data-integration.md)section for information on configuring the logger from your own server.
* **From the Efento Cloud Platform** – see the [**Efento Cloud**](https://docs.efento.io/efento-cloud/) section for information on configuring this setting remotely through the platform.
* **From the Efento mobile application** – connect to the logger and follow the relevant configuration path in the app.
* **Factory preconfiguration** – on request, Efento can supply devices with selected settings already configured according to your requirements. See [**Factory preconfiguration**](https://docs.efento.io/nb-iot-loggers/configuration/factory-preconfiguration.md) for the list of parameters that can be configured before shipment.

## **Configuration using the Efento mobile application**

In order to set the transmission interval from the Efento mobile app:

{% stepper %}
{% step %}
Connect to the logger, tap the gear icon in the upper-right corner, and under the **Cellular** section select **Transmission interval**.
{% endstep %}

{% step %}
Set the new transmission interval. It must be greater than or equal to the measurement interval.
{% endstep %}

{% step %}
Set the ACK interval. You can set it to:

* **Every time**- every data frame sent by the logger will require the ACK from the server. If the data has not reached the server, it will be retransmitted once the connection is reestablished
* **Custom setting** - you can set how often the device should require the ACK from the server. This is a good balance between making sure the data reaches the server and battery lifetime
  {% endstep %}
  {% endstepper %}


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://docs.efento.io/nb-iot-loggers/configuration/device-settings/transmission-interval.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.