> For the complete documentation index, see [llms.txt](https://docs.efento.io/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://docs.efento.io/nb-iot-loggers/configuration/device-settings/measurement-interval.md).

# Measurement interval

This parameter defines how often the logger takes a measurement. It can be set to any value from **5 seconds to 30 days**. By default, changing the measurement interval does not remove measurements already stored in the device memory.

## **Configuration methods**

You can configure these settings in several ways:

* **Remotely from server** – see the [**Integrations** ](https://docs.efento.io/nb-iot-loggers/integrations/direct-data-integration.md)section for information on configuring the logger from your own server.
* **From the Efento Cloud Platform** – see the [**Efento Cloud**](https://docs.efento.io/efento-cloud/) section for information on configuring this setting remotely through the platform.
* **From the Efento mobile application** – connect to the logger and follow the relevant configuration path in the app.
* **Factory preconfiguration** – on request, Efento can supply devices with selected settings already configured according to your requirements. See [**Factory preconfiguration**](https://docs.efento.io/nb-iot-loggers/configuration/factory-preconfiguration.md) for the list of parameters that can be configured before shipment.

## **Configuration using the Efento mobile application**

To change the measurement interval from the Efento mobile app, connect to the logger and tap the gear icon. Select **Measurement interval**, set the required value, and save the changes.

If you also want to remove measurements already stored in the logger’s internal memory, select the “Delete measurements?” checkbox in the same section before saving the changes.ve the changes.

## **Configurable parameters**

For more advanced configurations, the logger also supports two additional parameters:

| Parameter                     | Descritpion                                                            | Range           |
| ----------------------------- | ---------------------------------------------------------------------- | --------------- |
| **Measurement period base**   | Defines how often the sensor takes a measurement.                      | 1-65535 seconds |
| **Measurement period factor** | Multiplies the measurement period base for continuous sensor channels. | 1-65535 seconds |

For continuous channels (e.g. temperature, humidity), the effective measurement interval is calculated as:

**Measurement interval = Measurement period base × Measurement period factor**

For binary channels (e.g. open / close, leakage), measurements are taken according to the Measurement period base, regardless of the factor value. This allows mixed devices to use different effective measurement intervals for continuous and binary channels.

In the **Efento mobile application** and **Efento Cloud**, only the overall measurement interval is configured directly. In this case, the system automatically sets the **Measurement period factor to 1**, and the **Measurement period base** is set to match the selected measurement interval.

If you need independent values for both parameters (for example, to configure different measurement intervals for continuous and binary channels on a mixed-channel device), they can be configured remotely from a **custom server** or preconfigured by Efento prior to shipment as part of **factory preconfiguration**.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://docs.efento.io/nb-iot-loggers/configuration/device-settings/measurement-interval.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.