Device time
In order to operate properly, Efento NB-IoT logger has to set its internal time. After successful network registration, the device will automatically fetch the time from the network. From then on, all the measurements taken by the device will have the timestamp assigned. If for any reason the device is not able to fetch the time from the network, it will request the current time from the server it sends the data to (Efento Cloud or the customer's server).
If the logger sends the data to the customer's server, the server should respond to the current time request sent by the logger to the time endpoint (by default "t"). The response must be an ACK with the 2.05 Content code and the current UTC time (4-byte Unix timestamp) in the payload. The server can also update the logger's time at any moment by sending the current time in the logger configuration.